CONFIGURAÇÕES DE ALARME DOS DETECTORES DE GÁS
GÁS |
BAIXO |
ALTO |
TWA |
STEL |
O2 | 19,5% vol | 23,5% vol | N/A | N/A |
CO | 35 ppma, b | 70 ppmb | 35 ppma | 200 ppm |
H2S | 10 ppm | 20 ppm | 10 ppm | 15 ppm |
SO2 | 2,0 ppm | 4,0 ppm | 2,0 ppm | 5,0 ppm |
NO2 | 3,0 ppm | 6,0 ppmc | 3,0 ppm | 5,0 ppm |
Cl2 | 0,5 ppm | 1,0 ppm | 0,5 ppm | 1,0 ppm |
ClO2 | 0,1 ppm | 0,2 ppm | 0,1 ppm | 0,3 ppm |
CO2 | 0,5% vol | 1,0% vol | 0,5% vol | 3,0% vol |
PH3 | 0,3 ppm | 0,6 ppm | 0,3 ppm | 1,0 ppm |
NH3 | 25 ppm | 50 ppm | 25 ppm | 35 ppm |
HCN | 5,0 ppm | 10,0 ppm | 4,0 ppm | 4,0 ppm |
NO | 25 ppm | 50 ppm | 25 ppm | 25 ppm |
HCl | 2,5 ppm | 5,0 ppm | 2,5 ppm | 2,5 ppm |
H2 | 50 ppm | 100 ppm | N/A | N/A |
CH4 | 1,0% vol | 1,5% vol | N/A | N/A |
LEL | 10% LEL | 20% LEL | N/A | N/A |
PID | 100 ppm | 200 ppm | N/A | N/A |
Nota:
a. Para CO, o PEL OSHA é de 50 ppm. A Industrial Scientific usa a norma de ajuste de 1989 (35 ppm). Todos os pontos de ajuste de alarme são configuráveis em campo em toda a faixa do sensor. Exceções: LEL/CH4 - 0 a 60% e 0 a 3,0% por volume CH4. Havendo padrões, todas as configurações de alarme são baseadas no seguinte: os alarmes baixos são baseados nos valores PEL OSHA e/ou NIOSH; os alarmes altos são baseados em 2 vezes os valores PEL OSHA.
b. Os limites MSHA para CO são 50 ppm para um alarme baixo e 100 ppm para um alarme alto.
c. Os limites MSHA para NO2 são 5 ppm para um alarme alto.